Compresor Semi-hermético Frascold S10-52Y de 10CV

Referencia: S10-52Y
Compresor frigorífico Frascold, refrigerante R-134a, R-404A, trifásico 400V/50Hz PW.
Modelo S 10-52Y
Descripción
| Cylinders | 4 | 4 |
| Displacement @ 50 Hz | 51.5 m3/h [50Hz] | 1,818.98 CFH [50Hz] |
| Displacement @ 60 Hz | 61.8 m3/h [60Hz] | 2,182.78 CFH [60Hz] |
| Motor version [1] | 2 | 2 |
| Motor power (HP) | 10 | 10 |
| Motor power (kW) | 7.5 | 7.5 |
| Motor voltage at 50 Hz [2] | 380-420V/3/50Hz PWS V/ph/Hz | 380-420V/3/50Hz PWS V/ph/Hz |
| Motor voltage at 60 Hz [2] | 440-480V/3/60Hz PWS V/ph/Hz | 440-480V/3/60Hz PWS V/ph/Hz |
| PWS partition | 50-50 | 50-50 |
| Capacity control: CC + RSH | 100%-75%-50%-25% | 100%-75%-50%-25% |
| MRA, maximum operating current at 400V/50Hz and 460V/60Hz | 24.5 A | 24.5 A |
| LRA, maximum starting current at 400V/50Hz and 460V/60Hz, PWS motor | 59.1 A | 59.1 A |
| LRA, max starting current at 400V/50Hz and 460V/60Hz, DOL motor, PWS motor with DOL connection | 102.29 A | 102.29 A |
| Frequency min | 25 Hz | 25 Hz |
| Frequency max [3] | 87 Hz | 87 Hz |
| Protection device | INT69® Diagnose | INT69® Diagnose |
| Electric box class protection | IP56 | IP56 |
| Maximum pressure HP | 30 bar | 435.0 psi |
| Maximum pressure LP | 20.5 bar | 297.3 psi |
| Oil type [4] | POE32 | POE32 |
| Oil charge (3/4 of sight glass) | 2.9 l | 98.06 fl oz |
| Lubrication type | Centrifugal | Centrifugal |
| Net weight | 120 kg | 264.55 lb |
| Max Length | 550 mm | 21.67 inch |
| Max Width | 405 mm | 15.96 inch |
| Max Height | 405 mm | 15.96 inch |
| Rubber mounts diameter [2] | 50 mm | 1.97 inch |
| Rubber mounts height | 50 mm | 1.97 inch |
| Rubber mounts shore | 55 sh | 55 sh |
| Sound power level (-10/45, R404A) [5] | 76.5 dB(A) | 79.0 dB(A) |
| Sound pressure level @ 1m (-10/45, R404A) [5] | 68.5 dB(A) | 71.0 dB(A) |
| Compressor body material | Cast Iron | Cast Iron |
| Note | |
| [1] | Motor version: 1 = high and mid temperature, all refrigerants; 2 = low and mid temperature, all refrigerants; 3 = ECOinside, low temperature, R134a and R1234ze only |
| [2] | Others available on request |
| [3] | Maximum frequency depends on the working condition: see FSS3 (Frascold selection software) |
| [4] | Different kind of oil available on request |
| [5] | Sound pressure in free field, hemispherical model at 1 meter distance, 50Hz; PWL and SPL in different conditions are available on FSS3 |