Number of cylinders / Bore / Stroke  6 / 60 mm / 50 mm
Displacement 50/60 Hz (1450/1740 ¹/min)  73,80 / 88,60 m³/h
Voltage 1) 380-420V Y/YY -3- 50Hz PW
  440-480V Y/YY -3- 60Hz PW
Winding divided into  50% / 50%
Max. working current 2) 39.4 A
Max. power consumption 2) 23.5 kW
Starting current (rotor blocked) 2) 125.0 / 209.0 A
Motor protection  INT69 EX2
Protection terminal box  IP 66
Weight  219 kg
Max. permissible pressure (LP/HP) 3) 19 / 28 bar
Connection suction line SV  54 mm - 2 1/8 "
Connection discharge line DV  35 mm - 1 3/8 "
Lubrication  Oil pump
Oil type R134a, R404A, R407C/F, R507, R448A, R449A  FUCHS Reniso Triton SE 55
Oil type R22  FUCHS Reniso SP 46
Oil charge  2,7 Ltr.
Oil sump heater  230 V - 1 - 50/60 Hz, 180 W
Dimensions Length / Width / Height  738 / 439 / 429 mm
Sound power level LWA 4) 81,0 db(A) @ -35/+40°C
  78,0 db(A) @ -10/+45°C
  77,0 db(A) @ +5/+50°C
Sound pressure level LpA 4) 68,0 dB(A) @ -35/+40°C
  65,0 db(A) @ -10/+45°C
  63,0 db(A) @ +5/+50°C
1) Tolerance (± 10%) relates to the mean value of the voltage range. Other voltages and current types on request

All data are based on voltage rms values

PW = part winding, motors for part winding starting
(no start unloaders required)
2) - The stated value for the max. power consumption is valid for the adjusted power supply.
- Take account of the max. operating current / max. power consumption for designing fuses, supply lines and safety devices. Fuse: Consumption category AC3.
3) LP = Low pressure
HP = High pressure
4) Declared dual-number noise emission values are in accordance with ISO 4871. The corresponding uncertainty to the sound power level is KWA= 2,5 dB and to the sound pressure level is KpA = 2,5 dB. The values are valid for 50 Hz with the refrigerant R404A at the standard rating points according to EN 12900.
  • A-weighted sound power level LWA (re 1 pW), in decibel. The values were determined according to standard ISO 9614-2, accuracy class 2.
  • A-weighted sound pressure level LpA (re 20 µPa), in decibel. The values are calculated from the sound power level in accordance with ISO 11203: LpA = LWA - Q2 at a distance of d = 1m to the reference box.
Planos y dimensiones (en milímetros):

Artículos relacionados

Puede activar las notificaciones instantaneas para recibir avisos sobre su pedido.Las notificaciones instantaneas de la tienda estan activadas, puede desactivarlas si desea dejar de recibir avisos.Las notificaciones están bloqueadas, debe habilitarlas en su navegador web si desea recibir avisos.
Contacta con nosotros vía WhatsApp Contacta con nosotros vía WhatsApp
Comodo Secure Comodo Secure
Atención: utilizamos cookies propias y de terceros para realizar el análisis de la navegación de los usuarios y, así, mejorar nuestros servicios. Si continúa navegando, consideramos que acepta su uso. Puede cambiar la configuración u obtener más información aquí.